delivery contents:
New, soundproofed (69 db"A" (+/- 2.4) as the mean value of an all-round measurement at 7 measuring points) emergency power generator as backup power supply, designed for continuous operation around the clock.
The silencer hood is modular with generous doors for maintenance.
The built-in emergency power control, manufacturer Comap, type IG 200 is designed for uninterrupted reverse synchronization overlapping synchronization with control of your on-site network generator switchover.
Internal day tank (800 liters) in the base frame with drip tray. Optionally with leakage monitoring
Fuel consumption according to Volvo data sheet:
Consumption at 50% approx. 59 liters / hour | sufficient for approx. 13.5 hours
Consumption at 75% approx. 89 liters / hour | sufficient for approx. 8.9 hours
Consumption at 100% approx. 120 liters / hour | sufficient for approx. 6.6 hours
-/-
Speed Control | Speed governor class Electronic G3
exhaust gas temperature | Exhaust gas temperature °C 471
exhaust gas volume flow | Exhaust gas volume m³/h 5,556
Combustion air volume flow | Combustion air volume m³/h 2,280
Maximum exhaust back pressure | Maximum allowed back pressure mbar 100
thermal energy / waste gas | Heat reaction to exhaust week 375
thermal energy / charge air | Heat reaction to charge air KW -/-
thermal energy / cooling water | Heat reaction to cooling water week 187
thermal energy / radiation | Heat reaction to ambient week 18
Cooling air volume flow | Cooling air flow m³/h 36,000