delivery contents:
Still freely configurable emergency power system for your backup power supply
Optional with 40 ft. HC container, delivery time then + 4 weeks
The built-in emergency power control, manufacturer ComAp, type InteliGen4 500 is designed for uninterrupted reverse synchronization overlap synchronization with control of your on-site mains generator switchover.
Internal day tank (2,000 liters) in the base frame with drip tray. Optionally with leakage monitoring
Fuel consumption according to MTU data sheet:
Fuel consumption 50% l./h 335.5 = 225 g/kwh
Fuel consumption 75% l./h 510.2= 218 g/kwh
Fuel consumption 100% l./h 689.6 = 215 g/kwh
Autonomy at 75% of load h. ≈ 4 hours
-/-
Engine Fluids and Equipment
Type Lubricant Oil SAE 15W40
Amount of lubricating oil: 390 liters
Amount of coolant: 205 liters
Amount of coolant: 50 liters of charge air circuit
Battery capacity Ah 120
Number of batteries* 2 x 12 volt
-/-
Air data & energy balance:
Combustion air volume flow PRP: 3.7 m3/sec.
Exhaust gas flow PRP: -10.3 m3/sec
Exhaust gas temperature PRP: 535 °C
Max. exhaust back pressure mbar: 30.00
heat dissipation:
Cooling water: 1100 KW
Charge air circuit: 660
Radiant heat: 105 KW
Exhaust emissions:
NOx + NMHC: 1700 mg/Nm³
CO: 300 mg/Nm³
PM: 50 mg/Nm³