Stage V emergency power system can also be used as a backup power system for building feed-in 45 kVA with Yanmar motor with Bender insulation monitor for IT and TN networks
Stock No.: 1398
Completion:
Category:
Notstromaggregat Stationär
Generating Set:
portable
Gen Set:
silent Set
Technical Data Engine:
Engine Manufacturer:
Yanmar
Engine Type:
4 TNV 98 CT-IYE
Engine No.:
in Produktion
Engine Power:
39,6 KW
Cooling:
water-cooled
Starting:
electrical 12 V DC
Rotation:
1500 rpm
Fuel:
diesel
Fuel Consumption:
10,13 Bei 100 % Load
Emission Standard:
Stage V
Engine Size:
3,19L.
Amount of Oil:
10,5 L.
Consumption of Combustion Air:
194 m³/h
Cooling Air Volume:
4.234 m³/h
Exhaust Temperature:
480 °C
Exhaust Gas Quantity m3:
611 m3
Exhaust Gas Quantity kg:
kg
Technical Data Generator:
Generator Manufacturer:
Stamford AvK
Gen Set:
S1L2-N1
Gen No.:
in Produktion
Gen Power:
45 kVA
Gen Amperage:
Ampere
Short Circuit Current:
Ampere
Overload:
Ampere
Voltage:
400 / 231 Volt
Voltage Controller:
elektronisch AVR
Power Factor:
cos. - phi 0,8
Rotation:
1500 rpm
Control Unit:
Setup:
automatic start
Functions:
Hand & Remotestart
Switch:
gen switch 4 pole
Delivery:
set up
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Fuel Tank:
Setup:
Baseframe fuel Tank with Bassin
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Capacity / Litre:
100
Dimensions of unit:
Width ca. mm:
960
Height ca. mm:
1.260
Length ca. mm:
2.220
Weigth ca. KG:
1.040
Usage:
Stock No:
1398
State:
new
year of manufacture:
New
time of delivery:
ex work
Operating Hours:
Neu
Location:
Verl - Germany
Price plus VAT in €:
on request:
Reserved:
nein / no
delivery contents:
Stage V emergency power system can also be used as a backup power system for building feed-in 45 kVA with Yanmar motor with ISO monitor for IT and TN networks
Emergency power supply as a backup power system type WA YG 50 “S” with a robust YANMAR STAGE V diesel engine
Industrial diesel engine with electronic speed control and Stamford three-phase synchronous generator with fully electronic voltage control AVR. Motor and generator are elastically mounted on a common skid frame, installed in a soundproof enclosure with spacious lockable doors for maintenance, painted in RAL 3000.
Other additional features:
Tank capacity 100 liters, refueling directly at the tank from the inside
Internal start-stop automatic (ComAp AMF 25) with display of all important engine and generator messages. Functional digital display on the display. 4-pole generator switch integrated on the unit (generator).
Insulation monitor, 2 levels, make Bender IR 423 for mobile power generators. The ISOMETER® IR423 monitors the insulation resistance RF of an ungrounded AC system of 0...300 V to earth, which is fed by a mobile power generator in accordance with DIN VDE 0100-551 (VDE 0100-551). Also meets VDE 0100-717 (2005), GW 308, BGI 867 requirements
Socket combination: all sockets are individually protected (ISO monitored - IT system) for mobile operation as follows:
1 x CEE 400 volts 63 amps 6h | 1 x CEE 400 volts 32 amps 6h
1 x CEE 400 volts 16 amps 6h | 2 x 230 volts CEE and 1 x 230 volts Schuko
Additional CEE socket 63 amps 1H coded attached to the unit, this plug-in device is required for feeding into a building in the TN network according to VDE 0100-551 (2023.10)
The emergency power system as an emergency power supply is ready for operation and available from the Verl warehouse from January 2024.