delivery contents:
60 kVA LTP emergency generator with Deutz engine TCD 2.9 L4-SV, the latest exhaust technology with Stage V, emissions standard with DPF without AdBlue and Leroy Somer synchronous generator.
Emergency generator as a replacement generator for combined operation in the IT and TN network, with 2-stage Bender IR 423 insulation monitor with DEIF AGC-150 STANDALONE control. Installed on the sidewalk side of the emergency generator.
The base frame of the replacement network system is fully galvanized, designed as a collecting trough according to AwSV, the day tank is located in the collecting trough, optionally a powder coating of the collecting trough in RAL 9005 is possible. Modular sound insulation capsule with spacious doors for maintenance of the system. Sound insulation value: 64 dBA +/- 3 measured as an average in an all-round measurement at 7 measuring points.
Fully automatic load bank (dummy load) built into the body for gentle engine running and to prevent serious engine damage due to underload.
Load outlet on the back of the replacement generator set as follows:
IT network with Bender insulation monitoring:
1 x CEE 125 amps, 400 volts, IP 67, 6H coded
1 x CEE 63 amps, 400 volts, IP 67, 6H coded
1 x CEE 32 amps, 400 volts, IP 67, 6H coded
1 x CEE 16 amps, 400 volts, IP 67, 6H coded
3 x CEE 32 amps, 230 volts, IP 67, blue
1 x 230 volt Schuko socket, IP 67
TN network without insulation monitoring:
1 x CEE 123 amps, 400 volts, IP 67, 1H coded
1 x CEE 63 amps, 400 volts, IP 67, 1H coded
-/-
Fuel consumption, according to Deutz data sheet, at:
50% load = 6.7 liters / hour
75% load = 9.8 liters / hour
100% load = 13.7 liters / hour
-/-
Generator electronically controlled with VAR R180 with AREP+ winding