60 kVA Emergency generator as a replacement generator 60 kVA with Stage V Deutz engine TCD 2.9 L4-SV and Stamford generator
Stock No.: 1401
Completion:
Category:
Notstromaggregat Mobil
Generating Set:
portable
Gen Set:
silent Set
Technical Data Engine:
Engine Manufacturer:
Deutz
Engine Type:
TCD 2.9 L4-SV
Engine No.:
auf Anfrage
Engine Power:
53 KW
Cooling:
water-cooled
Starting:
electrical 12 V DC
Rotation:
1500 rpm
Fuel:
B0 Diesel
Fuel Consumption:
13,7 Liter at 100 % load
Emission Standard:
Stage V
Engine Size:
2,9L.
Amount of Oil:
L.
Consumption of Combustion Air:
m³/h
Cooling Air Volume:
m³/h
Exhaust Temperature:
460 °C
Exhaust Gas Quantity m3:
559 m3
Exhaust Gas Quantity kg:
kg
Technical Data Generator:
Generator Manufacturer:
Leroy Somer
Gen Set:
TAL 042H
Gen No.:
auf Anfrage
Gen Power:
60 kVA
Gen Amperage:
Ampere
Short Circuit Current:
Ampere
Overload:
Ampere
Voltage:
400 / 231 Volt
Voltage Controller:
elektronisch AVR
Power Factor:
cos. - phi 0,8
Rotation:
1500 rpm
Control Unit:
Setup:
automatic start
Functions:
Hand & Remotestart
Switch:
gen switch 4 pole
Delivery:
set up
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Fuel Tank:
Setup:
baseframe fuel tank with bassin
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Capacity / Litre:
250
Dimensions of unit:
Width ca. mm:
1.140
Height ca. mm:
1.647
Length ca. mm:
2.540
Weigth ca. KG:
1.600
Usage:
Stock No:
1401
State:
New
year of manufacture:
New
time of delivery:
ex work
Operating Hours:
Neu
Location:
Verl - Germany
Price plus VAT in €:
on request:
Reserved:
nein / no
delivery contents:
60 kVA LTP emergency generator with Deutz engine TCD 2.9 L4-SV, the latest exhaust technology with Stage V, emissions standard with DPF without AdBlue and Leroy Somer synchronous generator.
Emergency generator as a replacement generator for combined operation in the IT and TN network, with 2-stage Bender IR 423 insulation monitor with DEIF AGC-150 STANDALONE control. Installed on the sidewalk side of the emergency generator.
The base frame of the replacement network system is fully galvanized, designed as a collecting trough according to AwSV, the day tank is located in the collecting trough, optionally a powder coating of the collecting trough in RAL 9005 is possible. Modular sound insulation capsule with spacious doors for maintenance of the system. Sound insulation value: 64 dBA +/- 3 measured as an average in an all-round measurement at 7 measuring points.
Fully automatic load bank (dummy load) built into the body for gentle engine running and to prevent serious engine damage due to underload.
Load outlet on the back of the replacement generator set as follows:
IT network with Bender insulation monitoring:
1 x CEE 125 amps, 400 volts, IP 67, 6H coded
1 x CEE 63 amps, 400 volts, IP 67, 6H coded
1 x CEE 32 amps, 400 volts, IP 67, 6H coded
1 x CEE 16 amps, 400 volts, IP 67, 6H coded
3 x CEE 32 amps, 230 volts, IP 67, blue
1 x 230 volt Schuko socket, IP 67
TN network without insulation monitoring:
1 x CEE 123 amps, 400 volts, IP 67, 1H coded
1 x CEE 63 amps, 400 volts, IP 67, 1H coded
-/-
Fuel consumption, according to Deutz data sheet, at: