20 kVA very compact emergency power system for backup power supply 20 kVA Super soundproofed with Perkins engine
Stock No.: 1375
Completion:
Category:
Notstromaggregat Stationär
Generating Set:
stationary
Gen Set:
silent Set
Technical Data Engine:
Engine Manufacturer:
Perkins
Engine Type:
404A-22G1
Engine No.:
in Produktion
Engine Power:
18,4 KW
Cooling:
water-cooled
Starting:
electrical 12 V DC
Rotation:
1500 rpm
Fuel:
heating oil EN 590
Fuel Consumption:
5,3 Liter at 100 % load
Emission Standard:
TA-Luft
Engine Size:
2,22L.
Amount of Oil:
10,6 L.
Consumption of Combustion Air:
87 m³/h
Cooling Air Volume:
2.412 m³/h
Exhaust Temperature:
505 °C
Exhaust Gas Quantity m3:
236 m3
Exhaust Gas Quantity kg:
kg
Technical Data Generator:
Generator Manufacturer:
Mecc Alte
Gen Set:
NPE32-2M/4C
Gen No.:
in Produktion
Gen Power:
20 kVA
Gen Amperage:
Ampere
Short Circuit Current:
Ampere
Overload:
Ampere
Voltage:
400 / 231 Volt
Voltage Controller:
elektronisch AVR
Power Factor:
cos. - phi 0,8
Rotation:
1500 rpm
Control Unit:
Setup:
automatic start
Functions:
Hand & Remotestart
Switch:
gen switch 4 pole
Delivery:
set up
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Fuel Tank:
Setup:
Baseframe fuel Tank with Bassin
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Capacity / Litre:
90
Dimensions of unit:
Width ca. mm:
700
Height ca. mm:
1.650
Length ca. mm:
1.180
Weigth ca. KG:
Usage:
Stock No:
1375
State:
new
year of manufacture:
New
time of delivery:
ex work
Operating Hours:
Neu
Location:
Verl - Germany
Price plus VAT in €:
on request:
Reserved:
nein / no
delivery contents:
Very compact emergency power system with a nominal power of 20 kVA PRP, can be used in a small space with only 56 dbA
4-cylinder Perkins industrial diesel engine with a displacement of 2.22 liters
Fuel consumption at 50% load 2.90 liters / hour
Fuel consumption at 75% load 4.00 liters / hour
Fuel consumption at 100% load 5.30 liters / hour
Autonomy at 75% load ≈ 23 h
Type Lubricant Oil SAE 15W40
Lubrication power l.* 10.60
Type Coolant Antifreeze
Coolant capacity l.* 12.50
Suction filter paper cassette
Battery capacity Ah 50
Number of batteries* 1
Fuel system and energy balance
AC pump suction lift kPa 1
Combustion air volume flow at LTP output (110%) 87 m³/h.
Cooling air flow at LTP performance (110%) 2,412 m³/h.
Exhaust flow at LTP performance (110%) 236.4 m³/h
Exhaust gas temperature at LTP power (110%) 505.00 °C
Max. exhaust back pressure kPa 10.20
Exhaust heat at LTP power (110%) 16.60 kWt
Energy on coolant at LTP power (110%) 19.60 kWt
Radiant heat at LTP power (110%) 4.40 kWt
Control behind a protective flap
With 4-pin circuit breaker
Automatic control unit DSE4520, including:
- Voltmeter, frequency meter, ammeter
- Generator power display (kW, kV Ar, kV A & pf))
- Hour meter
- Tank content increase in %
- Protection against overload (kW & kV Ar)
- Low oil pressure protection with shut off
- Protection device against high coolant temperature with shutdown
- Protection against low fuel level
- Malfunction on the alternator, battery charger
- Protection device against overspeed (underfrequency)
emergency button
Terminal board for connection of the automatic switchboard
battery charger
Main switch on/off