250 kVAStand by generator 250 kVA emergency power system for building feed-in in RAL 9010 with 360 liter tank
Stock No.: 1410
Completion:
Category:
Notstromaggregat Mobil
Generating Set:
mobile
Gen Set:
silent Set
Technical Data Engine:
Engine Manufacturer:
Deutz
Engine Type:
TCD 2013 L06 4V
Engine No.:
in Produktion
Engine Power:
250 KW
Cooling:
water-cooled
Starting:
electrical 24 V DC
Rotation:
1500 rpm
Fuel:
heating oil EN 590
Fuel Consumption:
49,9 Liter at 100 % load
Emission Standard:
TA-Luft | Stage 3A
Engine Size:
7,15L.
Amount of Oil:
24 L.
Consumption of Combustion Air:
m³/h
Cooling Air Volume:
16.200 m³/h
Exhaust Temperature:
530 °C
Exhaust Gas Quantity m3:
909 m3
Exhaust Gas Quantity kg:
kg
Technical Data Generator:
Generator Manufacturer:
AvK Stamford
Gen Set:
UCDI 274 K1
Gen No.:
in Produktion
Gen Power:
250 kVA
Gen Amperage:
Ampere
Short Circuit Current:
Ampere
Overload:
Ampere
Voltage:
400 / 231 Volt
Voltage Controller:
elektronisch AVR
Power Factor:
cos. - phi 0,8
Rotation:
1500 rpm
Control Unit:
Setup:
automatic start
Functions:
parallel operation
Switch:
gen switch 4 pole
Delivery:
set up
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Fuel Tank:
Setup:
baseframe fuel tank with bassin
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Capacity / Litre:
360
Dimensions of unit:
Width ca. mm:
Height ca. mm:
Length ca. mm:
Weigth ca. KG:
3.500
Usage:
Stock No:
1410
State:
New
year of manufacture:
New
time of delivery:
ex work
Operating Hours:
Neu
Location:
Verl - Germany
Price plus VAT in €:
on request:
Reserved:
nein / no
delivery contents:
Emergency generator as a backup power system, soundproofed with approx. 69 db"A" measured in 7 meters with an all-round measurement in 7 meters at 7 measuring points (+/- 2.4 db"A") as a backup power system Type: WA-DG 250 "S"
Built on a 2-axle tandem chassis with a permissible total weight of 3,500 kg with a car ball head coupling, 12 volt version with 13-pin plug, walkable aluminum fenders.
Further features:
Internal day tank with 360 liters nominal capacity
Oil collection pan in the base frame
Electronic speed controller, control quality G 3
Automatic start with ComAp InteliGen4 / 200 control
Internal emergency power switchgear 4-pole generator switch 400 amps
Function: In the event of a power failure, the start command is passed to the diesel generator. When the rated speed and rated voltage are reached, the generator switch is switched on. When the mains returns, the automatic system monitors the mains voltage. When this is stable again, the switch back to mains operation takes place WITHOUT INTERRUPTION. The diesel generator is stopped after the cooling time and waits in automatic mode for the next power failure.
A motor-operated power switch and a power supply option are required on site.
The new emergency generator as a backup power system is ready for operation and available from the Verl warehouse.
Powerlock or Stäubli (MC sockets) can be offered as options. (Attention extension of delivery time).