300 kVA Emergency power system NSA as a backup power system with a nominal output of 300 kVA with Volvo Penta engine TAD 842 GE parallel to the main
Stock No.: 1380
Completion:
Category:
Notstromaggregat Stationär
Generating Set:
stationary
Gen Set:
silent Set
Technical Data Engine:
Engine Manufacturer:
Volvo Penta
Engine Type:
TAD 842 GE
Engine No.:
in Produktion
Engine Power:
273 KW PRP | 299 KW LTP
Cooling:
water-cooled
Starting:
electrical 12 V DC
Rotation:
1500 rpm
Fuel:
heating oil EN 590
Fuel Consumption:
65,1 Liter at 100 % load
Emission Standard:
TA-Luft
Engine Size:
7,7L.
Amount of Oil:
27 L.
Consumption of Combustion Air:
1.080 m³/h
Cooling Air Volume:
19.100 m³/h
Exhaust Temperature:
495 °C
Exhaust Gas Quantity m3:
2.896 m3
Exhaust Gas Quantity kg:
kg
Technical Data Generator:
Generator Manufacturer:
Stamford AvK
Gen Set:
S4L1D-D
Gen No.:
auf Anfrage
Gen Power:
300 kVA
Gen Amperage:
Ampere
Short Circuit Current:
Ampere
Overload:
Ampere
Voltage:
400 / 231 Volt
Voltage Controller:
elektronisch AVR
Power Factor:
cos. - phi 0,8
Rotation:
1500 rpm
Control Unit:
Setup:
automatic start
Functions:
emergency power
Switch:
gen switch 4 pole
Delivery:
set up
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Fuel Tank:
Setup:
baseframe fuel tank with bassin
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Capacity / Litre:
500
Dimensions of unit:
Width ca. mm:
1.350
Height ca. mm:
2.370
Length ca. mm:
3.770
Weigth ca. KG:
3.700
Usage:
Stock No:
1380
State:
new
year of manufacture:
New
time of delivery:
ex work
Operating Hours:
Neu
Location:
Verl - Germany
Price plus VAT in €:
on request:
Reserved:
nein / no
delivery contents:
New, soundproofed (69 db"A" (+/- 2.4) as the mean value of an all-round measurement at 7 measuring points) emergency power generator type WA-VG 300 "S" as backup power supply, designed for continuous operation around the clock.
The silencer hood is modular with spacious lockable doors for maintenance.
The built-in emergency power control, manufacturer ComAp, type InteliGen4 200 is designed for uninterrupted reverse synchronization overlapping synchronization with control of your on-site mains generator switchover.
Internal day tank (500 liters) in the base frame with drip tray. Optionally with leakage monitoring
Type Lubricant Oil SAE 15W40
Amount of lubricating oil: 27 litres
Type Coolant Antifreeze VCS (Yellow)
Amount of coolant: 51 liters
Battery capacity Ah 120
Number of batteries* 2 x 12 volt
-/-
Air Data & Energy Balance
Combustion air volume flow LTP: 16.2 m3/min
Cooling air flow LTP: 372 m3/min
Exhaust flow LTP: -/- m3/min
Exhaust gas temperature LTP: 495 °C
Max. exhaust back pressure kPa 10.00