680 kVA Emergency power system NEA as backup power supply with a rated output of 680 kVA with MTU engine 12 V 1600 G 20 F parallel to the mains
Stock No.: 1385
Completion:
Category:
Notstromaggregat Stationär
Generating Set:
stationary
Gen Set:
silent Set
Technical Data Engine:
Engine Manufacturer:
MTU
Engine Type:
12 V 1600 G 20 F
Engine No.:
1676000616
Engine Power:
576 KW G3
Cooling:
water-cooled
Starting:
electrical 24 V DC
Rotation:
1500 rpm
Fuel:
heating oil EN 590
Fuel Consumption:
126 Liter at 100 % load
Emission Standard:
44. BimschV |TA Luft
Engine Size:
21L.
Amount of Oil:
72,5 L.
Consumption of Combustion Air:
2.700 m³/h
Cooling Air Volume:
40.320 m³/h
Exhaust Temperature:
485 °C
Exhaust Gas Quantity m3:
m3
Exhaust Gas Quantity kg:
kg
Technical Data Generator:
Generator Manufacturer:
Stamford AvK
Gen Set:
HCI 544 F
Gen No.:
N23C127550
Gen Power:
680 kVA
Gen Amperage:
Ampere
Short Circuit Current:
Ampere
Overload:
Ampere
Voltage:
400 / 231 Volt
Voltage Controller:
elektronisch AVR
Power Factor:
cos. - phi 0,8
Rotation:
1500 rpm
Control Unit:
Setup:
automatic start
Functions:
parallel operation
Switch:
gen switch 4 pole
Delivery:
set up
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Fuel Tank:
Setup:
Baseframe fuel Tank with Bassin
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Capacity / Litre:
990
Dimensions of unit:
Width ca. mm:
2.060
Height ca. mm:
2.585
Length ca. mm:
4.860
Weigth ca. KG:
8.250
Usage:
Stock No:
1385
State:
new
year of manufacture:
New
time of delivery:
ex work
Operating Hours:
Neu
Location:
Verl - Germany
Price plus VAT in €:
on request:
Reserved:
nein / no
delivery contents:
Soundproof emergency power system NEA for outdoor installation as a backup power supply with a nominal output of 680 kVA with an MTU engine 12 V 1600 G 20 F optimized for emergency operation for grid parallel operation >10 MS
The built-in emergency power control is designed for uninterrupted back synchronization overlap synchronization with control of your on-site grid & generator switchover.
The Comap InteliGen4 200 is a diesel generator control unit for common parallel connection applications that supports both single and multiple generators in grid-connected or island operation.
Internal day tank (990 liters) in the base frame with drip tray. Optionally with leakage monitoring
Consumption according to MTU data sheet in exhaust-optimized version (NOx < 1500mg/m3 i.N.):
Fuel consumption approx. 50% (PRP) 68 l/h
Fuel consumption approx. 75% (PRP) 99 l/h
Fuel consumption approx. 100% (PRP) 128 l/h
Electronic controller ECU 8
Precision class control quality: G3
Number of cylinders 12 in V shape
Displacement: 21 liters
Bore / stroke 122 mm x 150 mm
Oil quantity 72.5 liters
Coolant water quantity 99 liters
Exhaust temperature: 485 °C
Exhaust volume flow 125 m³/min
Maximum exhaust back pressure: 15 kPA
Optionally available for an additional charge:
Automatic start with mains & generator switchover 4-pole
External ATS emergency power switch (AV/SV) for installation in the building and 4-pole mains generator switch
Function: In the event of a power failure, the start command is passed to the diesel generator. When the nominal speed and nominal voltage are reached, the generator switch is switched on. When the mains returns, the automatic system monitors the mains voltage. When this is stable again, the switchback to mains operation is made WITHOUT INTERRUPTION. The diesel generator is stopped after the cooling-down period and waits in automatic mode for the next power failure.
The emergency power generator with MTU engine is available at short notice from the Verl warehouse.